消防管道水压试验事故的处理
Quality Accident Treatment During Hydrotesting on a Fire一fighting Pipeline
浏览(1829) 下载(1)
- DOI:
- 作者:
- 王雄华
Wang Xonghua
- 作者单位:
- 武汉民生石油液化气公司
Wuhan,Hubei
- 关键词:
- 输水管道;压力试验;管道事故;原因;安全措施
water pipeline;pressure一test;accident;cause;disposal
- 摘要:
- 武汉民生石油液化气有限公司码头栈桥D325×8mm消防管道在水压试验时发生管道基础外移、波纹膨胀节破坏的事故。经分析认为,管道内形成气囊、波纹膨胀节固定支架设置不合理以及管墩配筋焊接不符合要求是事故的主要原因,通过采取相应措施,顺利完成第二次水压试验。
The accidents of pipeline foundation displacement & bellows expansion joint damage were happened during hydro一testing in a D325 x 8mm fire一fighting pipeline located at Wuhan Minsheng liquified petroluem gas Ltd. port jetty. By analyzing, the writer considers that the main accident causes are the air pocket formed in the pipeline, irrational fixed supports arrangement for bellows expansion joint & non一qualified welding nn pipe pier reinforcement etc..With corresponding measures,the second hydro一testing was completed smoothly.2001,4(4): 41-42 收稿日期:2000-8-27分类号:U653.99作者简介:王雄华,1990年毕业于石油大学(华东)化工设备与机械专业,一直在中国石油天然气第六建设公司从事技术管理工作,1998年12月借调武汉民生石油液化气有限公司任工程技术部经理。通讯地址:湖北省武汉市汉口,邮编:430022参考文献: