锌包钢接地极在输油气站场的应用
Application of Zinc Clad Steel Ground Electrode at Oil and Gas Stations
浏览(2257) 下载(2)
- DOI:
- 作者:
- 熊金根1, 许光达1, 张楠2
XIONG Jin-gen1, XU Guang-da1, ZHANG Nan2
- 作者单位:
- 1.中国石油西部管道公司科技信息服务中心 新疆乌鲁木齐 830012;
2.中国石油西部管道公司独山子输油气分公司 新疆独山子 833600
Western Pipeline Company of China Petroleum Technology Information Service Center
- 关键词:
- 站场设备;接地极;阴极保护;锌包钢;低电阻非金属模块;热镀锌接地角钢
station equipment;ground electrode;cathodic protection;zinc clad steel;low electric resis-tance nonmetallic module;hot dip galvanized angle steel for grounding
- 摘要:
- 交流电气装置的良好接地可使设备接地点在流过雷电流或系统短路电流时仍能保持较低电位,防止设备遭反击;但接地极也会导致被保护设施的阴极保护电流流出,造成站场设备因欠保护而腐蚀。文章分析比较了低电阻非金属模块、热镀锌接地角钢、锌包钢(CET)三种接地极的优缺点;介绍了采用锌包钢对阿拉山口输油站场接地网进行的改造,运行一段时间后检测发现:锌包钢接地体未出现腐蚀,对站场阴极保护系统影响很小。
Three kinds of ground electrodes are analyzed and compared, which are non-metallic module, hot dip galvanized angle steel and zinc clad steel. The results show that the first two ground electrodes have their own advantages, but they have a great influence on the cathodic protection system at a station, causing the station equipment to be under inadequate protection. The zinc clad steel is used at Alashankou oil station, and corrosion does not appear after running for some time. Zinc clad steel grounding has little effect on the cathodic system at the station.2013,6(6): 53-56 收稿日期:2012-12-21DOI:10.3969/j.issn.l001-2206.2013.06.015作者简介:熊金根(1965-),男,江西南昌人,高级工程师,1986年毕业于华中工学院电力系统及其自动化专业,现从事电力设计和输油气管道腐蚀与防护专业检测及技术研究工作。参考文献:
[1]何金良,曾雪嵘.电力系统接地技术[M].北京科学出版社,2007.
[2]张丽丽.浅谈非金属接地模块与金属接地极的差异与施工[J].中国对外贸易(英文版,China's Foreign Trade ), 2012,(4):396.
[3]吴运策,胡铁军,唐瑶.几种小同接地材料在小同土壤土质条件h的对比分析[A].中国气象学会S13第十届防雷减灾论坛——雷电灾害与风险评估[C].沈阳中国气象学会,2012.584-587.
[4]徐洪振,樊刚,钟毅,等.锌包钢连续挤压包覆技术[J].南力金属,2007,(3):1-3.
[5]周佩朋,王森,李志忠,等.耐蚀性金属接地材料研究综述[J].电力建设,2010,31(8):50-51.
[6]杨万国,刘同刚,徐风刚,等.油气站场埋地管网阴极保护案例及对对比分析[J].石油工程建设,2011,37(5):46-49.